AS3000-02127B
Revised 05-03
Catalog Section 75
(00-02-0525)
Automatic Engine Controller
FWMurphy
AS3000 Model
■
■
■
■
■
Auto crank disconnect
Multi-attempt starting
Fault warning and shutdown
Reduced panel wiring
Simple set set-up
Lamp test: Close to negative DC (±3V)
to activate.
Description
Easy setup of operating options using circuit
board links.
•
•
The AS3000 provides automatic start up, fault mon-
itoring and shutdown control for engine driven
applications. The unique two-module design, with a
single interconnecting lead, gives reduced panel
wiring and installation. This simple, compact unit is
ideally suited to small engine and generator panels.
DC input protection: ±50 VDC maximum.
AC Inputs
Generator AC Hz meter output, 0 – 5V.
Product Specification
Power supply
Magnetic pickup: 3 – 60 VAC, 50Hz – 10 kHz.
Generator AC: 600 VAC maximum (L-L or
L-N), 50/60 Hz.
Continuous voltage range: 8 – 35 VDC
Key features
Brown out voltage: < 5 VDC for 2 secs
(recovery to 8V)
Outputs
Multi-attempt cranking with auto crank disconnect
•
•
Fuel: positive DC (transistor), 5A max.
Crank, preheat: positive DC (transistor),
2A max.
Common alarm, fault lockout: negative DC
(transistor), 300mA max.
Generator Hz. Meter: 0-1mA (@ 45 - 65 Hz).
Automatic or manual modes, selected by front
facia pushbuttons. Control inputs for optional
security keyswitch.
Blackout voltage: 0V for 50mS (from 10V,
recovery to 5V)
Overvoltage withstand: 50 VDC for 5 sec-
onds (to SAEJ1810 load dump immunity)
User inteface module: front of panel mounted,
92mm square DIN cut-out. Environmental
sealing to IP65
•
Reverse voltage withstand:
100 VDC continuous.
Physical
Panel interface module: DIN rail mounted
PCB tray.
Dimensions: see “System Overview” on page 2.
Operating temperature: 14 to 149°F (-10 to
+65°C).
Relative humidity: 95% @ 140°F (60 °C).
Environmental protection: AS3000 front:
IP65, NEMA4.
Back of User Interface and Panel interface
require weather-proof enclosures for outdoor use.
Vibration: ISO 88528 pt.9, & 3 axis 3g.
•
Current consumption (standby): 50mA.
Current consumption (max): 500mA (plus
output loads).
Fault shutdown and indication system. Low oil
•
pressure, high coolant temperature and auxil-
iary inputs are fitted to both modules, allowing
use with engine mounted fault switches or
panel mounted SWICHGAGE® units.
DC Inputs
Oil pressure, coolant temp, auxiliary and
charger faults: Closed to negative DC
(±3V) on fault.
Speed sensing (auto crank disconnect and over-
•
speed shutdown) is via magnetic pickup, gen-
erator AC or remote contact. Speed calibration
is automatic and adjustment free.
Weight:
Remote start positive: Open from positive
DC to start.
AS3000 User Interface: approx. 9 oz. (250g).
AS300 Panel Interface: approx. 6 oz. (160g).
Shipping Weight: 1 lb. 4 oz. (554 g.).
Shipping Dimensions: 7-3/8 x 5 x 3-1/8 inch.
(187 x 127 x 79 mm.).
Remote start negative: Close to negative DC
(±3V) to start.
Mains charger/charge alternator fail warning LED.
•
AS3000-02127B page 1 of 2
|
Miller Electric Welding System Regency 250 User Manual
MTD Tiller 216 410 000 User Manual
Nintendo Video Games 45496902971 User Manual
Nokia Cell Phone OT V570 User Manual
Numark Industries DJ Equipment WS User Manual
NuTone Speaker ISA 445 User Manual
Oricom Telephone BT9500 User Manual
Palsonic CRT Television 6159G User Manual
Panasonic Webcam DMC TZ30 User Manual
ParaBody Home Gym 805106 User Manual